45 tz 41

Input/Output

  • TZ-41 is designed as "Self Powered Isolation" and transformation ratio is 1:1.
  • Input current is 0 to 20 mA, but customers can use input current ranges 0 to 5 mA, 0 to 20 mA or 4 to 20 mA.
  • Having 1:1 isolation the output current will of course be the same as the input current, e.g., 0 to 5 mA, 0 to 20 mA, 4 to 20 mA.
  • TZ-41 will provide 0 to 5 V or 1 to 5 V output.

Output load and Accuracy

  • TZ-41 can operate into a load of up to 600 W.
  • Accuracy is a function of load resistance.
  • Standard accuracy is ± 0.1% with a 250 W load and ambient temp. of 23 ±1°C.
  • For loads other then 250 W accuracy changes as shown below.
  • Example load 450Ω
  • Standard accuracy: ±0.1%
  • Additional error (+200 W): ±0.1% - 0.2% = -0.1% to -0.3%
    (-0.1%/100Ω at load > 250Ω)